Model No.: DDS228
Specification: Single Phase Two Wire
Meter Type: Electronic
Display: LCD, 6+2 digits, Eg.: 123456.78 kWh
Usage: 50Hz or 60Hz Active Energy Consumption
Advantage: Large Scale Integrated Circuit and SMT Technique
Size: 158x110x59mm
Mounted:
Wall mounted, Three screw fixed installation
Enclosure Material: ABS Anti-flaming with PC transparent window Anti-UV Terminal Cover: Short and Extend type Energy Record : 1. The Non-volatile memory shall have a minimum retention time of 10 years 2. Forward and Reverse Active energy consumption Standard : 1. IEC62052-11: 2003 ; IEC62053-21:2003 Connection : 1. Direct connection Up to 100A 2. Current Transformer Type 1.5(6)A Communication: RS485 & Infrared By RS485 cable within 1000m you can read energy data Protocol: 1. DLT645-1997 with Far infrared communication 2. MODBUS-RTU widely used in foreign countries (Baud rate: 1200bps ~ 9600bps)
|
Accuracy |
Class 1.0 |
Rated voltage |
220V, 230V, 240V 110V( optional ) |
Operation voltage range |
Un±20% |
Insulation capabilities |
AC voltage withstand 2kV for 1 minute Impulse voltage withstand 4kV - 1.2/50μs waveform |
Rated current |
1.5(6), 5(20), 10(40)A, 15(60), 20(80), 30(100). |
Operation current range |
0.05Ib~ Imax |
Starting current |
0.004Ib |
Rated frequency |
50Hz or 60 Hz |
Internal power consumption |
Voltage Circuit ≤1.0W 5VA; Current Circuit ≤1VA(Ib) |
Interface |
Optical coupler (So corresponding to DIN 43864) |
Impulse valence Ra |
0,5 or 1.0 Wh/imp |
Max. operation temperature |
-25°C ~ +70°C |
Relative humidity |
≤ 85% |
1. OEM
2. ODM
3. HUABANG Distributor
The picture is for reference only. Please adhere to the original products in case of any mistake!
MOQ | 1pcs |
Package | 100pcs per carton |
Size | 46.5x26x27mm |
Gross Weigth |
13Kg |